Tag Archives: Charging Station

IR Modulation Processing Algorithm Development – Part I

Posted 23 May 2017

As you may recall from previous posts, I have been collaborating with my long-time friend and mentor John Jenkins on the  idea to use square-wave modulation of the charging station IR beam to suppress ‘flooding’ from ambient IR sources such as overhead incandescent lighting and/or sunlight.

More than likely, If it is possible to implement a software processing algorithms to recover steering information from potentially corrupted data, it will have to be housed on a dedicated processor.  So, I decided to set up a separate test setup using two processors – one to generate a square-wave modulation waveform, and another to receive that waveform through an IR link.  The link can then be modified in a controlled way to simulate link losses and/or ‘flooding’.  The initial hardware setup is shown below.

Initial test bed verification using 12cm separation

Scope shot showing transmitted and received waveforms, 12cm separation

Algorithm test bed with IR link range set to 78cm

Then I ran my little test program on the receiver processor that simply acquires 100 samples at roughly 20 samples/cycle and then prints out the results.  The following two images are Excel plots of the results for 12cm & 78cm separation.

As can be seen from these two plots, the 12 & 78cm separation values provide a reasonably good simulation of the ‘very good’ and ‘reasonably crappy’ signal conditions.

Next I verified that I can successfully ‘flood’ the receiver with my portable battery-operated IR signal generator.  I monitored the transmitted  and received waveforms, without and then with flooding.  In both cases, the  bottom trace is the 5V square-wave transmitted signal, shown at 2V/div, and the top trace is the received signal shown at 1V/div.  The ground for both traces is the same line on the scope screen.

78cm separation, no flooding signal. Bottom trace is transmit @ 2V/cm, top is receive @ 1V/cm, ground for both is same line

78cm separation, with flooding signal. Bottom trace is transmit @ 2V/cm, top is receive @ 1V/cm, ground for both is same line

Applying flooding signal with battery-operated IR signal generator

As can be seen in the scope photos, I can indeed produce almost 2V of ‘flooding’ using the IR signal generator, so I should be able to determine whether or not a particular recovery algorithm is successful at suppressing flooding effects.

Stay tuned

Frank

 

 

 

 

Charging Station System Integration. New Sunshade Testing

Posted 19 May 2017

While working with John Jenkins on the modulated IR beam idea, I decided to run some tests with the current 4-detector design, to see how the new sunshade with center divider was affected by  ambient IR on a bright sunny day.  So, I disabled Wall-E2’s motors and then placed it at several different critical spots in the entry hallway.  At each location I used my little IR test generator to mark the beginning and the end of the test for that location, and then moved on to the  next one.  The locations are shown in the following photos, in the order that the tests were run.

Position 1: Near where Wall-E2 transitions from wall-tracking to IR beam homing

Position 2: This is where Wall-E2 has been winding up when it homes on the outside sunlight instead of the IR beam

Position 3: Here Wall-E2 should be firmly fixated on the IR beam

These results, combined with my earlier IR response tests with a single phototransistor are encouraging, because it is clear that at least in this case, Wall-E2 should have no difficulty discriminating between the ambient IR and the charging station IR beam.

I ran some homing tests, which Wall-E2 handled with ease; unfortunately God had already turned the lights out on this side of the world, so the tests weren’t in the presence of daylight IR interference.  I’ll do some more real-world discrimination testing tomorrow, and  I am  hopeful that the new sunshade-with-divider version will be successful, at least for this part of the house.

Stay tuned,

Frank

 

 

IR Light Follower for Wall-E2, Part XI. Center Divider Investigation

Posted 16 May 2017

One of the suggestions John Jenkins made during his visit, in addition to the idea of modulating the IR beam to suppress ‘flooding’ from ambient IR sources, was the idea of placing an opaque divider between the left and right halves of the detector array.  He thought that I might even be able to reduced the detector array from four to two phototransistors and still get good homing performance, assuming that each of the two detectors had sufficiently wide beamwidths to accommodate off-axis IR beam intercepts.  The current detectors have a +/- 12 º beamwidth, but are arrayed in such a way as to provide well over 60 º aggregate coverage.  To do the same thing with just two detectors would require parts with considerably wider beamwidths.  the TAOS TSL267 (another one of JJ’s suggestions) has an approximately +/-30 º beamwidth at the half-response points, so they seem almost ideally suited for  this application.  As a major added bonus, the TAOS parts feature a photo-diode integrated with an op-amp to address the dynamic range issue mentioned by John.  The diode operates in its linear range, and the op-amp amplifies the IR signal to useful levels.  The only fly in the ointment is that the op-amp gain isn’t adjustable, and its output limits at fairly low light levels – bummer!

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download

In order to investigate  the opaque divider idea, I decided to run some bench angular response tests using my robot’s 4-detector array with and without a center divider.  I printed out a copy of the compass rose graphic I had hanging around from my magnetometer project (one of my more spectacular failures) and set up a bench test with Wall-E2 and my little IR test source, as shown below.

Angular response test setup

Closeup of the ‘sunshade’ cowling (black rectangular opening) around the 4-detector array

Closeup of sunshade with divider installed

The results without the center divider were about as expected, with about +/- 45 º coverage, as shown in the Excel plot below

Response vs angle for 4-detector array, without center divider

+/- 60 deg response vs angle for 4-detector array, without center divider

With the divider, the response appears to be about the same (note here that the ‘with divider’ response is flipped left/right from the ‘no divider’ case – oops!)

+/- 30 deg response vs angle for 4-detector array, without center divider

Note in the above ‘detail’ view that the response curves for the two center detectors (DET2 & DET3) seem to be very symmetric about the 0 º point, as expected.  What this also shows is that just these two detectors could probably be used for homing, if off-axis beam detection weren’t a consideration.

+/- 30 deg response vs angle for 4-detector array, with center divider

The ‘with divider’ plot above shows a significant difference from the ‘no divider’ plot, right at the center.  In the ‘no divider case, the DET1 & DET2 responses are very nearly the same, but in the ‘with divider’ case they are significantly different, and almost perfectly anti-symmetric about the center.  This  should allow more precise detection of small left/right deviations from the beam centerline, and therefore more precise homing.

Stay tuned!

Frank

 

 

IR Phototransistor Sensitivity/Dynamic Range Study

Posted 05/14/17

In a previous post, I mentioned that John Jenkins, mentor and old friend, had  some ideas regarding my Wall-E2 robot’s problems with homing in on an  IR beam in the presence of ambient IR sources like overhead incandescent lighting and/or sunlight streaming in through windows and doors.   John pointed out that this was really a system dynamic range issue, and it was likely that, as currently configured, the IR phototransistors were running out of dynamic range (saturating) well before the 10-bit A/D’s on the AtMega SBC.  In order to get the detector sensitivity up to the  point where Wall-E2 could ‘see’ the IR beam far enough (1.5-2m) away to avoid hanging up on the lead-in rails (see this post  and this post for details), I had to use a very high value collector resistor (330K), which reduces the dynamic range significantly.

In a subsequent email conversation, John suggested that the proper way to handle this problem was to reduce the collector resistor to the point where the detector doesn’t saturate under the worst case ambient IR conditions, and then add amplification as necessary  after the detector stage to get the required sensitivity.  John’s point was that as long as the detector response is relatively linear (i.e., it’s not saturated), then there shouldn’t be any loss of information through the stage, so a later linear amplification stage will allow the desired IR signal to be detected/processed even in the presence of interference.  However, if the detector stage saturates due to interference, then it’s basically ‘game-over’ in terms of the ability to later pull the desired signal out of the noise.

This wasn’t exactly what I wanted to hear, as adding the required post-detector amplification stage wasn’t going to be particularly easy – there’s not much left in the way of free real-estate on Wall-E2’s main platform (there’s plenty of room on the second level, but putting stuff there requires inter-level cabling and is a major PITA).  As I was thinking this, I had a flashback to similar conversations with John from 40-45 years ago, when we were both design engineers in a USG design lab; the usual outcome of such ‘conversations’ (to the uninitiated these might be mistaken for shouting matches) was that my circuit got ‘simplified’ by the addition of 50% more parts – but could then withstand a nuclear attack in the middle of a snowstorm at the South Pole!

Anyway, back in the present, John suggested I run some experiments designed to determine the ratio of IR field intensity to collector current for a the  phototransistors I was using, so the proper collector resistor value to be computed to utilize the available detector dynamic range without driving it into saturation.  His suggestion was to not  use a collector resistor at all, but to simply connect the collector to +VDC through a current meter, and then expose the detector to worst-case ambient conditions.  I didn’t particularly like this idea, because I only have a manual non-recording multimeter, and I wanted to record the data for later analysis.  So, I decided to program up one of my small SBC’s with analog input capability (in this case, a Pololu Wixel), and set up to measure the voltage drop across  a 10  Î© precision resistor in the collector circuit.  The hardware setup is shown in the following photo

Hardware setup for IR Phototransistor Response Experiment

Before and after collecting ‘field’ data, I made a collection run on the bench, using my IR LED test box, with the following results.  As can be seen in the plot, the maximum voltage drop across the 10Ω resistor was approximately 200mV, or about 20mA.

IR detector response bench test. Nose-to-nose with my IR test source

Bench test with IR LED test generator

 

To collect the ‘field’ data, I placed the SBC in different locations around the house, and recorded A/D values.  For these experiments I was using an example Wixel app that printed out the A/D values for all 6 analog inputs, scaled such that the maximum reading was equivalent to the SBC board voltage (3.3V) in millivolts.  In other words, the maximum A/D reading was approximately 3375, or about 3 mV/bit

Location 1: Looking out glass doors on south side of house

Location 2: Direct sunlight through window on south side of house

Location 3: Kitchen floor, looking toward entrance hall and atrium

Location 4: Entry hallway, looking toward atrium. This is the usual starting location for charging station homing tests

Location 5: Entry hallway near door to atrium

These results were not at all what I expected.  Either there is something wrong with the experimental setup, or the ambient light IR field intensity isn’t anywhere near as  strong as expected.  If the data can be believed, the ambient conditions are significantly weaker than the bench-test conditions, which were basically nose-to-nose with my IR test LED.  So, if my planned  double-check of the hardware doesn’t find any problems, then I’ll change the resistor value from 10Ω to 100Ω and repeat the tests.

17 May 2017 Update

After thoroughly reviewing the hardware setup, I concluded that everything was working properly, but that the 10Ω load resistor simply didn’t provide sufficient drop for reliable measurements.  So, I changed out the 10Ω resistor for 100Ω, and repeated the tests, with the following changes:

  • As before, I started the run by performing a ‘nose-to-nose’ test to verify proper operation, but this time I measured the detector current using a multimeter. The  result was about 15mA maximum current.
  • At each of the 5 locations, I started with a short nose-to-nose section (not shown in the plots) to make sure the detector was operating properly
  • At location 2 (the direct sunlight location), I physically oriented the detector for maximum response.
  • After location 5, I placed the detector on the charging station’s IR beam reflector boresight at about 0.5m distance, and physically oriented the detector for max response.
  • I calculated the detector current for each reading, and plotted that rather than the raw reading.  To calculate the detector current for each measurement, I subtracted the  detector reading from the corresponding 3.3VDC supply  voltage measurement and divided by 100.

The results of these tests are shown in the plots below:

 

These results are pretty interesting.  As I’m sure John would point out, the direct sunlight response of about 0.2 mA is about 20 times the value required to saturate the phototransistor with  the current 330KΩ.  No wonder I was having interference problems – oops!

Stay tuned!

Frank

 

 

 

 

 

 

Charging Station Design, Part XIV – Modulated IR Beam Study

Posted May 10, 2017

A couple of weeks ago my old friend and mentor John Jenkins was visiting the area and stopped in for a couple of days.  Naturally I had to show him my Wall-E2 robot, complete with autonomous charging capability.  Just as naturally (if you believe in Murphy’s law), Wall-E2 refused to cooperate.  Instead of homing in on the charging station, it blissfully homed in on the sunlight streaming in through the atrium, bypassing the charging station entirely!

After John got through laughing, he mentioned that he knew of some other IR-following robotics projects where the designers used a modulated IR beam to allow the robot to discriminate between general IR background noise and the intended signal.  So, I decided to start a feasibility study to see if I could incorporate some sort of modulation into the design of the charging station, without completely overtaxing either the charging station, or the robot, or both!

I started with the idea that I could easily add square wave modulation to the IR beam by simply switching the LED off & on at some reasonable rate (say, 500Hz).  The problem occurs on the other end (the robot), as it will somehow have to a) detect the square wave signal, and b) still have the ability to home in on the modulated signal – i.e. still be able to determine  signal variation across the four photo-transistor  array.

To investigate,  I created a square wave generator using an Adafruit Trinket, and a square wave receiver using an Arduino Uno, as shown in the following photo

Adafruit Trinket SBC used for generating the square wave signal, and an Arduino UNO used as the receiver

Square wave signal from the Trinket

The first step was to see if the Arduino Uno was fast enough to accurately detect the square wave pattern, so I simply grabbed 100 samples from the input pin using digitalRead() with a delay of about 1/10 of the waveform period.  Then I plotted the data in Excel, as shown below:

Digital samples from Arduino Uno ‘receiver’

As can be seen from the plot, there are plenty of samples per cycle, well above the Nyquist rate for the dominant signal term.

Next, I moved the square wave signal to an analog input on the Uno, and reprogrammed to collect analog values vice digital ones, as shown below:

Analog readings with 500Hz square wave input

As can be seen,  the analogRead() function is plenty  fast enough to accurately reproduce the digital square wave signal, with about 10-13 samples/cycle.  So, at least in principle I should be able to detect a square-wave-modulated IR beam, and determine its ‘field strength’ (analog reading when the beam is ON) for homing purposes.

Stay tuned!

Frank

 

Charging Station System Integration. Part IV

Posted xx  April 2017

While doing the hallway testing that led to the  discovery of the overhead IR ‘noise’ problem and the design of a ‘sunshade’ to suppress that noise and implementation of the flashlight reflector idea for the IR LED, I discovered several other problems with the operating system, as follows:

  1. Once the software detects an IR signal, it switches in to IR homing mode, but the only way back out again is to either execute the avoidance routine if it isn’t in need of a charge, or by connecting to the charger and then disconnecting once the battery is fully charged.  There’s no provision for error cases, like getting stuck on on of the lead-in rails.
  2. The charging station disconnect maneuver needs work – it doesn’t back far enough away, and doesn’t turn far enough to actually get away from the charging station.
  3. The routine that monitors the charging state needs work. On several occasions it detected ‘end of charge’ when one of the chargers momentarily switched  from ‘charging’ to the ‘finished’ state and back to ‘charging’.  The software should not declare ‘end of charge’ until both chargers’ status is ‘finished’, and the software should employ  integration  to handle momentary state changes.

Item 1 – Exit provisions for IR homing code

This item actually turned into a full-blown rewrite of Wall-E2’s operating system software structure.  As I looked at the code to determine the best way to implement the required error case detection/responses, it became apparent that the problem was ‘baked-in’ to the software system design, and would have to be addressed at that level.  So, I went ‘back to the drawing board’ (in this case to Microsoft Visio) and reworked the system design to allow Wall-E2 to detect and respond appropriately to error conditions in any mode, not just the normal wall-following one.  The revised structure charts are shown in the following PDF document:

Loader Loading...
EAD Logo Taking too long?

Reload Reload document
| Open Open in new tab

Download

In the revised structure, the system always returns to the ‘Determine Op Mode’ block after each pass through the system, without getting stuck anywhere.  This means that the ‘GetOpMode()’ routine has the opportunity on each pass through loop() to detect error situations (like the ‘stuck’ condition) and respond by switching to the appropriate branch of the structure tree.

Item 2 – Charging Station Disconnect Maneuver

This one was just a matter of tweaking the ‘degrees’ parameter to the ‘RotateCWDeg((bool bRotateCW, int degrees_to_rotate)’ function.  I started out with degrees_to_rotate = 90, but then tweaked it to 120 for better disconnect performance.

Item 3 – Charge State Monitoring

In the current operating system, a function called ‘MonitorChargeUntilDone()’ is called when the robot detects that it is connected to the charging plug.  This function goes into an infinite loop, waiting for the charging status to change from ‘charging’ to ‘finished’.  While in this loop, the charger 1 and charger 2 status lines are read in about once per second, until either both ‘finished’ outputs are TRUE, or the  BATT_CHG_TIMEOUT_SEC backup timer elapses.  This logic seems OK, but I have observed several inappropriate disconnect instances where only one of the two ‘finished’ outputs were TRUE.   I suspect that there is a period of time where these two status lines oscillate from FALSE (not yet finished) to TRUE (finished) and back again, before finally settling down on ‘finished’.

In my new strategy of eliminating all inner loops, the   ‘MonitorChargeUntilDone()’ function will no longer be used.  Instead,  the ‘Charge Mode’ block of the new software structure chart (shown below) will be implemented.

Updated Charge Mode Structure Chart Detail

This block will be executed on each pass through the loop() function, as long as the ‘Determine Op Mode’ block returns with the current mode set to ‘MODE_CHARGING’.  When/If the ‘Both Cells Charged’ or the ‘Charger Timeout’ reached ‘if’ statements return TRUE, then the ‘Disconnect’ function will be triggered, which will cause the robot to immediately disconnect and back away from the charging station.  This in turn will cause the ‘Determine Op Mode’ block to output a different mode value (assumed to be, but not necessarily ‘MODE_WALL_FOLLOWING’), and the appropriate portion of the overall structure diagram will be executed.

I’m away from my robot at the moment, at a bridge tournament in Gatlinburg, Tennessee, so I can’t immediately implement and test the above changes.  However, I will be back home next week and hope to have everything running by the end of May. If everything works out, I may have a fully functioning charge station operational by then, and a ‘more-or-less’ fully autonomous Wall-E2 robot.  It will be interesting to see what kind of trouble Wall-E2 can get into with the much longer run times that should be possible with autonomous charging capability.

Stay tuned!! 😉

Frank

 

 

 

 

 

Charging Station System Integration. Part III

Posted 15  April 2017

In my previous post on this subject, I described some IR homing tests with and without the overhead incandescent lights, and  the development of a ‘sunshade’ to block out enough of the IR energy from the overhead lamps to allow Wall-E2 to successfully home in on the IR beam from the charging station.  At the conclusion of that post, I had made a couple of successful runs using a temporary cardboard sunshade, and thought that a permanent sunshade would be all that I needed.

However, after installing the sunshade (shown below), I discovered that the homing performance in the presence of overhead IR lamps was marginal when the robot’s offset distance from the wall was more than about 50 cm.

Sunshade, oblique view

Sunshade, side view

Sunshade, front view

Apparently  the IR interference was causing the robot to not respond to the IR beam until too close to miss the outer lead-in rail.  This issue was explored in an earlier post, but I have repeated the relevant drawings here as well.

 

Tilted gate option. The tilt decreases the minimum required IR beam capture distance from about 1.7m to about 1.0m

Capture parameters for the robot approaching a charging station

When the robot is ‘cruising’ at more than about 50 cm from the tracked wall,  the IR interference from the overhead lamps prevents the robot from acquiring the charging station IR beam until too late to avoid the outer lead-in rail, even in the 13 º tilted rail arrangement in the first drawing above.

 

So, what to do?  I am already running the IR LED at close to the upper limit of the normal operating current, so I can’t significantly increase the IR beam intensity – at least not directly.  I can’t really increase the size of the ‘sunshade’ dramatically without also significantly affecting the IR beam detection performance.  What I really needed was a way of increasing the IR beam intensity  without increasing the LED current.  As it turns out, I spent over a decade as a research scientist at The Ohio State University ElectroScience Lab, where I helped design reflector antenna systems for spacecraft.  Spacecraft are power and weight limited, so anything that can be done to improve link margins without increasing weight and/or power is a  good thing, and it turns out you can do just that by using  well-designed reflector dishes to focus the microwave communications energy much like a flashlight. You get more power where you want it, but you don’t have to pay for it with more power input; the only ‘cost’ is the insignificant added weight of the reflector structure itself – almost free!  In any case, I needed something similar for my design, and I happened to have a small flashlight reflector hanging around from a previous project – maybe I could use that to focus and narrow the IR beam along the charging station centerline.

LED flashlight reflector

So, using my trusty PowerSpec PRO 3D printer and TinkerCad, I whipped up an experimental holder for the above reflector, as shown below

Experimental 3D-printed flashlight reflector holder

Reflector mounted on experimental holder

IR LED mounted on reflector

A couple of quick bench-top tests convinced me I was on the right track; At 1m separation between the IR LED/reflector combination and the robot, I was able to drive the robot’s phototransistors into saturation (i.e. an analog input reading of about 20 out of 1024 max), where before I was lucky to get it down to 100 or so.  However, this only happened when I got the LED positioned at the reflector focal point, which was tricky to do by hand, but not too bad for a first try!

Next, I tried incorporating the reflector idea into the current charging station IR LED/charging probe fixture, as shown in the following photo. This was much closer to what I wanted, but it still was too difficult to get the IR LED positioned correctly, and this was made even more difficult by the fact that I literally could not see what I was doing – it’s IR after all!

New reflector and old charging station fixture designs

However, the reflector focusing performance should be (mostly) the same for IR and visible wavelengths, so I should be able to use a visible-wavelength LED for initial testing, at least.  So, I set up a small white screen 15-20 cm away from the reflector, and used a regular visible LED to investigate focus point position effects.  As the following photos show, the reflector makes quite a difference in energy density.

Green visible LED, hand-positioned near the focal point

Pattern without the reflector

Next, I used my Canon PowerShot SX260HS digital camera as an IR visualizer so I could see the IR beam pattern. As shown below, the reflector does an excellent job of focusing the available IR energy into a tight beam

IR beam visualized using my Canon PowerShot SX260HS digital camera

IR LED, without reflector

Next, I made another version of the reflector holder, but this time with a way of mounting the LED more firmly at (or as near as I could eyeball) the reflector focal point.

Reflector holder modified for more accurate LED mounting

With this modification, I was able to get pretty good focusing without having to fiddle with the LED location, so I set up some range tests on the floor of my lab.  With LED overhead lighting (not incandescent), I was able to get excellent homing performance all the way out to 2m, as shown in the following photos and plots

Range testing the IR reflector in the lab. Distance 2m

IR Detector response vs orientation at 2m from reflector, in the lab

IR reflector beam pattern at 2m, visualized using digital CCD camera

After this, I decided to try my luck again out in our entry hallway, with the dreaded IR interference from the overhead lighting and/or sunlight.   I installed the lead-in rails in the ’tilted’ arrangement, and then performed a response vs orientation test with the robot situated about 2.5m from the IR LED/reflector assembly, in natural daylight illumination with the overhead incandescents OFF.  This produced the curves shown in the plot below.

Robot response vs orientation test setup, 2.5 m from tilted lead-in rails & LED/reflector assembly

IR detector response vs orientation test, 2.5 m from IR LED/Reflector assembly

In  the above Excel plot, the individual detector response minimums can be clearly seen, with minimum values in the 200-300 range, and off-axis responses in the 800-1000 range.  This should be more than enough for successful IR homing.

After seeing these positive responses, I ran some homing tests starting from this same general position.  In each run, the robot started off tracking the right-hand wall at about 50 cm  offset.  One run was in daylight with the overhead lights OFF, and another was in daylight with the overhead lights ON.  As can be seen in the videos below.

Both of the above test runs were successful.  The robot started homing on the IR beam almost immediately, and was successfully captured by the lead-in rails.

So, it is clear the reflector idea is a winner – it allows the robot to detect and home in on the IR beam from far enough away to not miss the capture aperture, even in the presence of IR interference from daylight  and/or  overhead incandescent lighting.

Next step – reprint the IR LED reflector holder with the charging probe holder included (I managed to leave it out of the model the last time), and verify that the robot will indeed connect and start charging.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charging Station System Integration. Part II

Posted 07 April 2017

After getting the wall-following mode re-implemented in the ‘new-improved’ Wall-E2 operating system, I re-enabled the IR homing part of the code, only to discover that Wall-E2 thought it could see the IR homing beam  everywhere, in the atrium, even though the IR homing LED wasn’t even in the room (and was turned OFF, besides)!  This didn’t make a whole lot of sense, until I realized Wall-E2’s sensors were ‘seeing’ IR from the overhead floodlamps.  I confirmed this by having my ‘lovely assistant’ wife turn the atrium lights on & off and monitoring the detector outputs.  Same thing for the entry hallway (see data below)

I thought I had solved this problem way back when I first started working with the IR detection/homing idea back in October of last  year.  In that initial post  where I investigated  the  OSEPP IR Light Follower’, I found I had to turn OFF the LED track lights in my lab in order to avoid swamping the detector array.  Over the next month or so this project evolved into a custom designed array of  Oshram SFH309FA-4 phototransistors (see  http://gfpbridge.com/2016/11/ir-light-follower-wall-e2-part-vi/), and as part of this I discovered that the Oshram devices weren’t at all sensitive to the LED track lighting in my lab.  From this I concluded (erroneously as it now turns out!) that I didn’t need a ‘sunshade’ at all, which allowed for a much simpler installation on the robot (see  http://gfpbridge.com/2016/11/ir-light-follower-wall-e2-part-vii/).  Finally, when this module was transferred from the 3-wheel test bed to the Wall-E2 and combined with the charging status display panel, we arrived at the ‘final’ arrangement shown in the following photo

IR detector module (red) shown beneath charging status display panel (blue)

This worked great for all my in-lab IR homing tests with my all-LED overhead track lighting, but as soon as I started testing out in the rest of the house, the overhead incandescent and halogen lamps swamped out the detectors. So, it was back to the drawing board – again :-(.

The first thing I did was to confirm that the IR detectors were indeed getting swamped by the overhead lighting, and that it was possible to prevent this by some sort of shielding.  I started with a wrap-around cardboard shield that completely covered the IR detector module, as shown below, and placed the robot on the floor of the entry hallway in a normal ‘wall-following’ position

Sunshade V0. Not very practical, but does set the baseline for the rest of the tests

Test position for 07 April 2017 sunshade tests

 

With this setup, Wall-E2 was pretty much deaf to the overhead lamps, showing no reaction to cycling the lights.  Of course, this configuration would also completely prevent it from detecting the charging station IR beam, but….

Next I modified the above V0 cover to allow a bit more visibility, as shown below:

Sunshade V1 oblique view

Sunshade V1 front view

This version is still a bit too restrictive for normal IR beam detection/homing, but was worth a shot for testing purposes.  With this setup, the overhead lighting  is noticeable, as shown below.

Sunshade V1 at sunshade test position. Lights ON four times for 5, 5, 5 and 10 sec

As can be seen from the plot, the V1 sunshade responds to the overhead lamp IR with an average A/D reading about 700 out of 1024.

Next, I modified  the sunshade again so that it would just allow the IR detector module to ‘see’ straight ahead, on the theory that that would be the minimum requirement for successful IR beam detection/homing.  With this setup, the overhead lamp response was stronger, but still not completely overbearing;  the IR detector response to the overhead lights averages A/D values of about 600 out of 1024.

Sunshade V2 oblique view

Sunshade V2 front view.  Note IR detectors visible from directly in front

IR detector response to overhead lamps. ON three times for 5 sec each

When I ran a homing test  with the V2 sunshade in my lab (with LED overheads, not incandescent), the robot homed successfully from about 1 m away, with the following IR detector/homing performance

In-lab (LED overhead lighting) charging station homing performance with V2 sunshade

In the above homing test, the IR detector values started out at approximately 900, 200, 450 and 750, respectively.  This means I could set the IR beam detection threshold at, say, 400 and still have a 200-count noise margin in both directions (200 down from the overhead IR flooding value, and 200 up from the typical 1-meter IR beam intensity).  From the movie it is obvious that the minimum IR reading is switching back and forth between at least two detectors, so I think it is safe to say that IR homing would occur even in the presence of a 600 unit noise level, as the 200 or lower reading switched between detectors.

Next, I moved the charging station into the entry hall so I could test IR homing performance with the overhead lights on and off.  My prediction was that Wall-E2 should be able to home successfully in both cases.  For the test, the charging station lead-in rails were oriented in the preferred ’tilted’ orientation, as that should give the best homing performance, as shown in the photos below:

Hallway IR homing test setup

Robot shown in captured position. Note lead-in rail ’tilt’ relative to the wall

I made three runs; Lights ON, lights OFF, and Lights ON, as shown in the three video clips below:

 

As can be seen in the videos, Wall-E2 successfully homed to the charging station with the overhead lights OFF, but not with them ON – bummer!

So, further testing will be required to determine the particulars of the two failed runs, and what – if anything – can be done about it.

After moving my laptop  out into the hallway so I could capture telemetry from the robot while also filming the runs, and checking everything out, I made two successful IR homing runs – one with the overhead lights ON, and another one with them OFF.  I captured telemetry from both runs, and was clearly able to distinguish between the lights ON and OFF scenarios.  The videos and the telemetry plots are shown below:

08 April 2017 Hallway Test2 with V2 Sunshade – Lights OFF

08 April 2017 Hallway Test2 with V2 Sunshade – Lights ON

From the above plots, the lights ON & OFF conditions are readily recognizable.  In the ‘OFF’ condition, the ‘background noise’ is at about 600-700, and the IR beam is at 100-200.  In the ‘ON’ case, the noise level is higher (lower count), at about 150-250, but the IR beam is lower too – around 50-150.  I guess this makes some sort of sense, as the IR energy from the charging station beam is a separate, additive source relative to the overhead lighting.  Also, both plots show good motor response curves – the left & right motor speeds are obviously being adjusted rapidly in response to IR detector changes.

So, at this point I’m pretty convinced that the V2 sunshade is working, so I plan to print up a permanent version that will (hopefully) simply slide on to the front of the existing charge status display panel.

Stay tuned!

Frank

 

 

 

 

 

Charging Station Design, Part XIII – More PID Tuning

Posted 28 March 2017

After my cleanup-and-label campaign documented in my last post, I was ready to get back to PID tuning for homing in on the charging station.  When my grandson was here, he pretty much took over my primary work area, so I was forced to move my bench-top testing range to another part of my bench.  This was not quite as convenient for reprogramming the bot, but it did give me a bit more distance between the initial bot position and the IR LED in the charging station, as shown in the following photo

Wall-E2’s new PID test range

I started out by going back to the simplest possible PID setup – namely (p,i,d) = (1,0,0) and ran a series of range tests, as shown in the following video.

As is evident in the video, Wall-E2 has no difficulty homing into the charging station when initially placed near the edge of the bench, but won’t home properly from the other side.  After thinking about this for a bit, I came to the conclusion that the reason for this is that the center of the charging station is physically located near the edge of the bench, so when the bot starts at that edge, it is actually close to the centerline of the charging station, and therefore is almost perfectly lined up at the start. When starting from the other side however, the initial position is not lined up with the charging station centerline and therefore has to make more of a correction to get lined up.  From this I hypothesized that the PID setting of (1,0,0) doesn’t provide enough of a wheel-speed correction to make the required turn.

So, next I tried a PID of (2,0,0), and this worked much better, as shown in the following video

As can be seen from the first run above, the robot is doing a much better job of homing, but unfortunately ran into the left side rail instead of being captured.  This turns out not to be a PID tuning issue, but rather a problem with the IR beacon pattern relative to the lead-in rail arrangement.  The line from the robot’s starting position to the IR LED unfortunately intersected the outside of left lead-in rail instead of the inside.

As an experiment to confirm the IR beam pattern hypothesis, I printed up an auxiliary part to restrict (not collimate, as that implies shaping) the beam to a narrower pattern, as shown in the following photos  ( taken with a digital camera with a wavelength range that covers the  IR wavelength being used)

This experiment ‘worked’ in the sense that it showed that the IR beam was no longer visible outside the lead-in rail aperture, but it also made it so narrow that the robot had to be right on the centerline to sense the IR beam at all.  Although this solves the problem of hitting the rail, it would make it very difficult for the robot to ever find the charging station in the first place when approaching at the typical wall-following standoff distance.

So, although I plan to do a bit more fine-tuning of the PID parameters, it appears that the basic homing problem is solved,  but the challenge now is  getting the robot into a position where it can home in on the IR beam without running into a side rail.  The current wall-following algorithm doesn’t have a set stand-off distance, so the robot may be ‘cruising’ at anywhere from 10-70 cm from the wall being tracked.  Assuming that one lead-in rail is against the wall, the IR led is located about 20 cm out, and the front end of the outside lead-in rail is about 35 cm out.  When the robot is just captured by the outside rail, its centerline is about 16 cm out.  The angle from the IR LED to the center of the robot at this point is about 11-12 º.  So, assuming the robot is wall-following and at some point intersects the IR beam and starts homing, the angle from the robot to the IR LED has to be less than 11-12 º or the robot will not be captured by the lead-in rails.  The situation is shown graphically in the following diagram.

Capture parameters for the robot approaching a charging station

As shown above, if the robot is ‘cruising’ at 45 cm from the wall, then it has to start homing from no less than 1.7 m or so from the charging station in order to get captured by the lead-in rails.  This is  a large, but impossible distance.  The robot can currently home from about 1 m out, so getting out to 1.7 m might be as easy as increasing the IR LED current;   it is  currently running at about 30 mA, and it is rated for 100.

Another possibility is to angle the capture gate out slightly with respect to the wall. There’s no real reason the charging station rails need to be parallel to the wall – it’s just my neat-freak mentality that makes me do things that way.  If I angle it such that the inside lead-in rail touches the wall at both its forward and trailing ends, that will angle the beam out at about 13 º, and move the minimum capture distance in to about 1.0 m, as shown in the following diagram.  1.0 m is just about where the robot is capturing now – yay!!

Tilted gate option. The tilt decreases the minimum required IR beam capture distance from about 1.7m to about 1.0m

So, it appears that tilting the capture gate is the way to go; this doesn’t cost anything but a slight ding in my ‘neat-freak’ index, and should  eliminate or greatly reduce problems with charging station capture failures.

Stay tuned,

Frank

 

Charging Station Design, Part XII – A Pause to Clean Up

Posted 22 March 2017

This last weekend was devoted to a whirlwind visit by the St. Louis family, which includes my 13-year old, growing-like-a-weed, 3D printing enthusiast grandson.  So, I didn’t get a whole lot of time to work on Wall-E2’s problems, as Danny basically took over my entire lab ;-).  So, now that the horde (can one 13 year-old kid constitute a ‘horde’?) has departed, I can get back to some sort of normalcy and make some progress.

At the end of my last post on this subject, I had concluded that I needed to go back and verify the details of the IR homing hardware and software, as the results I was getting didn’t make sense.  So, I set up some experiments where I could carefully watch the raw output from all 4 IR detectors, and the changes from physically blocking one IR LED at a time.  This experiment convinced me that something was definitely wrong with the hardware; at least one detector appeared to be dead, and it also looked like blocking one detector affected the outputs of more than one – strange!

So, back to the hardware; After dismounting the combined charge status display panel/IR detector module and separating the two, and physically inspecting the IR detector module I  found  a bad solder joint (what – a bad solder joint!?  I  never make bad solder joints! – must have been someone else!) on one of the detector connections to the interface  header.

After repairing the bad solder joint, I carefully worked my way through the cabling maze on Wall-E2 to the microcontroller end of the IR detector cable, to verify proper connection on that end.  The connections looked good, so I did some more testing, only to find that one of the IR detector outputs appeared to be dead – it’s analog reading stayed around 4-500 no matter what I did.  Some more physical inspection revealed the problem – my 4-pin IR detector cable was connected to A2-A6 on the Mega board, but I was reading A1-A5, so the A1 input was essentially ‘open-circuit’ – oops!

After fixing this booboo, things started to perk up and act a *lot* more normally! ;-).  However, instead of immediately going back to testing mode, I decided that I needed to get serious about labeling and indexing cables (I use red fingernail polish to index one end of each connector to the corresponding microcontroller pin) and connectors  on Wall-E2, so I would have less trouble in the future with the large number of ribbon cables and loose wires now festooning the robot.   Fortunately I have my wonderful Brother P-touch label maker to help me with this task. As an aside, if you are a ‘maker’ hobbyist like myself, a label maker is an absolute godsend, and I can’t recommend the Brother P-touch highly enough.

After my labeling and cleanup campaign, Wall-E2 is  a lot more self-documenting, as shown in the following photos